Features:
- High accuracy
- Replaceable sensor head
- Wall or ceiling mounted
- External control signals
- 0-20.0 PPM Range
- Low Cost
Related Files

S-100 Info Sheet
109.6 k
Specifications:
The Series 100 ozone controller is designed to be operated as part of an ozone generator control circuit or alarm system.
Features:
- High accuracy
- Replaceable sensor head
- Wall or ceiling mounted
- External control signals
- 0-20.0 PPM Range
- Low Cost
Related Files
| S-100 Info Sheet | |
| 109.6 k |
| Sensor type | Gas Sensitive Semiconductor (GSS) |
| Measurement range | |
| Low concentration Ozone Head | 0.000 to 0.500 ppm |
| High concentration Ozone Head | 0.00 to 5.00 ppm |
| Accuracy | |
| Low concentration Ozone Head | +/- 0.010 ppm (0 to 0.100 ppm) |
| +/- 10% (0.100 to 0.500 ppm) | |
| High concentration Ozone Head | +/- 10% (0.20 to 5.00 ppm) |
| T90 response time (standard) | |
| Low concentration Ozone Head | 60 seconds |
| High concentration Ozone Head | 35 seconds |
| Operating temperature range | -5°C to 50°C |
| Relative humidity limits | 5% and 95% |
| Removable/replaceable sensor heads | Yes |
| Controller/Switch Specifications | User adjustable high and low control and switching set points |
| User adjustable control ‘dead band’ | |
| External trigger signal for control and switching (user supply): 12 volts, 150 mA | |
| LED status indicators: High/low/within control band, fault/failure | |
| Power Requirements (User supplied): 12 VDC, 400 mA | |
| Unit Interface (power in, control signal out): RJ45 connector. | |
| Height (with monitor): 64 mm; Diameter of base: 130 mm |