Inline Process Dissolved Ozone Monitor
Accurate dissolved ozone monitor
Inline high accuracy dissolved ozone monitor for process water flows. 1 PPB resolution with 0.001-2.000 PPM range. Excellent for bottled water or semiconductor processing applications.
Features:
- Very accurate
- 1 PPB resolution
- Quick installation
- low cost
- simple setpoint adjustment on panel
Related Files

MOZ-44P Info Sheet
169.7 k

MOZ-44P Manual
97.8 k
Specifications:
Inline high accuracy dissolved ozone monitor for process water flows. 1 PPB resolution with 0.001-2.000 PPM range. Excellent for bottled water or semiconductor processing applications.
Features:
- Very accurate
- 1 PPB resolution
- Quick installation
- low cost
- simple setpoint adjustment on panel
Related Files
| MOZ-44P Info Sheet | |
| 169.7 k | |
| MOZ-44P Manual | |
| 97.8 k |
| Range | 0.001 – 1.999 mg/l (ppm) |
| Resolution | 1 PPB |
| Accuracy | +/- 0.5% over range |
| Hysteresis | 0.1 mg/l (ppm) |
| Power requirements | 2 Watts at 120V/230V, 50-60 Hz, +10/-15% |
| Output current loop settings | 4-20mA or 0-20 mA – selectable via switch on rear |
| Sampling water flowrate | 10-30 GPH |
| Relays | Two Independent SPDT relays, 5A @ 220V resistive |
| Enclosure | IP 00 - standard 1/4DIN |
| Dimensions | 96 x 96 x 94 mm deep (3.8 x 3.8 x 3.7") |
| Operating temperature | 0 - 115 deg F (45 deg C) |
| Relative Humidity | 0 - 85% non-condensing |
| Tolerances from temperature changes | +/- 1% at each 10 deg C away from 20 deg C |
| Status of relays | Amber LED on the front panel indicate when reading is over the preset limit |
| Settings of output channels | via screwdriver slot at the front panel |
| Maximum load on output channels | 120V/50-60Hz, max. 0.1A |
Related Products:
| Dissolved Ozone Kit |